Littelfuse SymCom PC-200-LLC-GM Liquid Level Control
Littelfuse SymCom PC-200-LLC-GM Liquid Level Control

Part Number:
PC200LLCGMManufacturer:
Littelfuse SymComManufacturer Part Number:
PC-200-LLC-GMThis part is non-returnable. Use the Spec-Sheet provided to confirm all product specs.
Regular Price
USD
$
149
90
Shipping Details
Weight:
2 lbsDimensions:
7 x 7 x 5 inchesUPC:
07945899772Technical Details
Specifications
Input Power: | 190-240VAC |
Input Hz: | 60/50 |
Min Operating Temp: | -40°C = -40°F |
Max Operating Temp: | 70°C = 158°F |
Mounting Method: | OT08-PC socket |
Safety Marks: | UL, CE |
Brand: | SymCom |
Documentation
Additional Information
Littelfuse SymCom PC-200-LLC-GM Liquid Level Control is a liquid level control relay 190-240VAC 8-pin plug-in used to control conductive liquid pumping operations in a pump-up or pump-down application.
This unit has a 2 Input Liquid Level Control with an adjustable sensitivity knob (4.7k to 100k ohms) that is set according to the resistance level at which you want the probes (sold separately) to sense the conductive liquid. The unit has a built-in debounce time delay that prevents the relay from energizing if the probe resistance momentarily goes above or below the sensitivity set-point (due to liquid splashing in the tank).
The unit operates its internal relay based on inputs from a high and low probe and a common reference (when a conductive tank is used) or common probe (when a non-conductive tank is used).
Pump-up application: when the liquid level drops and the low probe resistance increases above the sensitivity setpoint, the relay energizes to run the pump and fill the tank. When the liquid level rises and the high probe resistance decreases below the sensitivity setpoint, the relay de-energizes to stop the pump.
Pump-down application: when the liquid level rises and the high probe resistance decreases below the sensitivity setpoint, the relay energizes to run the pump and empty the tank. When the liquid level drops and the low probe resistance increases above the sensitivity setpoint, the relay de-energizes to stop the pump.
The unit can also be configured to work with a single probe input and a common reference (or common probe).
The PC-200-LLC-GM Model is compatible with Gems' series 16M liquid level control.
Disclaimer: Littelfuse products are not designed for, and shall not be used for, any purpose (including, without limitation, automotive, military, aerospace, medical, life-saving, life-sustaining or nuclear facility applications, devices intended for surgical implant into the body, or any other application in which the failure or lack of desired operation of the product may result in personal injury, death, or property damage) other than those expressly set forth in applicable Littelfuse product documentation. Warranties granted by Littelfuse shall be deemed void for products used for any purpose not expressly set forth in applicable Littelfuse documentation. Littelfuse shall not be liable for any claims or damages arising out of products used in applications not expressly intended by Littelfuse as set forth in applicable Littelfuse documentation. The sale and use of Littelfuse products is subject to Littelfuse Terms and Conditions of Sale, unless otherwise agreed by Littelfuse. "Littelfuse" includes Littelfuse, Inc., and all of its affiliate entities.